Heat Calculation ExamplesEXAMPLE 1: A tubular Bushing Heater is required to heat a 10 gallon tank of water. Initial water temperature is at room temperature of approx. 70° F. Final water temperature required is 100° F. Water must be brought up to final temperature in 1 hour. No additional water is added to the system. Customer has an ideal system with zero heat loss. Calculate the wattage required to heat only the water (ignore the tank for this example.). SOLUTION: 1. Basic equation for initial material heatup:
2. From properties of liquids and engineering conversions charts:
a. 1 gallon of water = 8.3 pounds (lbs) 3. Plug numbers into equation and solve:
= 7.29.8 watts Add 20% allowance = 730 watts x 1.20 = 875 watts EXAMPLE 2: Customer requires Flanged Tubular Heater to heat a 200 gallon tank of water. Initial water temperature is at room temperature of approx. 70° F. Final water temperature required is 150° F. Water must be brought up to final temperature in 3 hours. No additional water is added to the system. Tank has approximately 25 square feet of 1Ú4Ó thick uninsulated steel walls and a total tank weight of 254 lbs. Water surface area is approximately 12 square feet and is open to the environment. Tank is installed in a room at 70° F. SOLUTION: 1. Remember basic equations: a. For material and tank heatup
b. For heat loss from water surface:
c. For heat loss from walls of uninsulated steel tank
2. From properties of liquids chart, engineering conversions chart, and heat loss graphs:
Total wattage = 12,974 w + 238 w + 1800 w + 260 w = 15,272 w (15.3 kw) Total wattage with 20% contingency = 18,326 watts (18.3 kw) EXAMPLE 3: Same conditions as example 1 except tank and water are already up to final operating temperature. No additional water or other material is added to system. How much wattage is required to maintain the tank and water at the 150° F temperature in the 70° F room? SOLUTION: 1. The tank and water are already up to the final operating temperature, therefore, no heat is required to bring the system up to temperature. Heatup wattage = 0 2. The only factors affecting heat requirements are heat losses from the water surface and tank walls at operating temperature. 3. Heat equations to counteract heat losses at operating temperature a. For heat loss from water surface: wattage loss = Liquid surface area (sq. ft.) x watts/sp. ft. loss at final temp b. For heat loss from walls of uninsulated steel tank: wattage loss = tank wall surface area (sq. ft.) x watts/sq. ft. loss at final temp 4. Use same heat loss - watts/sq. ft. values from graphs as in example 2: a. Heat loss from water surface at final temp = 300 w/sq. ft. b. Heat loss from uninsulated steel walls at final temp = approx. 25 w/sq. ft. x 8.3 (averaging factor) = 20.8 w/sq. ft. 5. Plug numbers into equations and solve: wattage (ave. loss from water surface) = 12 sq. ft. x 300 w/sq. ft. wattage (ave. loss from tank walls) = 25 sq. ft. x 20.8 w/sq. ft. Total wattage (to maintain temp) = 3600 w + 520 w = 4120 w (4.1 kw) Total wattage with 20% contingency = 4944 watts (4.9 kw)
|
|||||||||||||||||||||||||||||||||||||
| |
||||||||||||||||||||||||||||||||||||||
![]() |
||||||||||||||||||||||||||||||||||||||
phone: 905.859.8225 fax: 905.859.4691 |
||||||||||||||||||||||||||||||||||||||
toll free: 1.877.674.9744 |
||||||||||||||||||||||||||||||||||||||
|
||||||||||||||||||||||||||||||||||||||
|
||||||||||||||||||||||||||||||||||||||
| Terms & Conditions | ||||||||||||||||||||||||||||||||||||||
| Questions or comments about this site? Contact webmaster | ||||||||||||||||||||||||||||||||||||||
| © National Plastic Heater Sensor & Control Co. 2000 | ||||||||||||||||||||||||||||||||||||||