Heat Calculation Considerations and Equations
Room heating calculations with factors for construction, outdoor temperatures, and other variables considered.
- WALLS, ROOF, OR FLOORS WITH MINIMUM 3" INSULATION
- WALLS, ROOF, OR FLOOR WITH 1" INSULATION
- STUD WALL FINISHED BOTH SIDES - NO ADDED INSULATION
- WOOD FLOORS
- BRICK WALL - 8" THICK
- WOOD SHEATHING ON STUDS
- CEILING (NO INSULATION)
- CORRUGATED METAL WALLS OR SINGLE GLASS WINDOWS
*Must also add wattage for air exchange - for 3 air exchanges per hour with 70° F temperature difference between room and outside - multiply cubic feet volume by 1.06 watts. For other temperature differences use equation:
Temperature Difference
--------------------------------------------------------------------------------
x 1.06 x CU.FT. Volume - see example below
70
Heat Calculation Example (use graph for approximate heat loss)
ROOM WITH FOLLOWING DIMENSIONS AND CONSTRUCTION FEATURES NEEDS TO BE HEATED TO 70¡ F WITH A WORSE CASE OUTSIDE TEMP OF 20° F
20 FT LONG X 10 FT WIDE X 8 FT
STUDDED WALLS FINISHED BOTH SIDES
NO WINDOWS/CEILING HAS NO INSULATION/WOOD FLOOR
A. OUTSIDE WALLS:
2(20 FT X 8 FT) + 2(10 FT X 8 FT) = 480 SQ. FT.
480 SQ. FT. X 5 W/SQ. FT. = 2400 WATTS (HEAT LOSS)
B. CEILING:
20 FT X 10 FT = 200 SQ. FT.
200 SQ. FT. X 11 W/SQ. FT. = 2200 WATTS (HEAT LOSS)
C. FLOOR:
20 FT X 10 FT = 200 SQ. FT.
200 SQ. FT. X 7 W/SQ. FT. = 1400 WATTS (HEAT LOSS)
D. ADDITIONAL HEAT FOR AIR EXCHANGES:
20 FT X 10 FT X 8 FT = 1600 CU. FT.
1600 CU. FT. X 50 F/70 F (RATIO) X 1.06 WATTS/CU. FT. = 1211 WATTS
RESULT: 2400 W (A) + 2200 W (B) + 1400 W (C) + 1211 W (D) + 1.2 (CONTINGENCY) 8640 W OR 8.64 KW
Room heat losses per °F - For various constructions
A. TO CALCULATE STRUCTURAL HEAT LOSSES:
- DETERMINE AREA IN SQ. FT. FOR EACH SECTION OF WALL, CEILING, AND FLOOR
- SELECT CORRESPONDING VALUE FOR SQ. FT. OF EACH SECTION AT LEFT SIDE OF GRAPH. MOVE FROM LEFT TO RIGHT ALONG HORIZONTAL LINE TO INTERSECTION POINT WITH CURVE FOR APPROPRIATE CONSTRUCTION
- MOVE DOWN VERTICALLY TO HEAT LOSS VALUE (EXPRESSED IN WATTS PER DEG F)
- REPEAT FOR 1-3 AS REQUIRED FOR ALL SECTIONS
- ADD HEAT LOSS VALUES OF ALL SECTIONS TO DETERMINE TOTAL HEAT LOSS PER DEGREE FOR COMPLETE STRUCTURE
- MULTIPLY TOTAL HEAT LOSS PER DEGREE BY DESIGN TEMPERATURE DIFFERENCE SET DESIRED INSIDE
TEMPERATURES AND TYPICAL WORSE CASE OUTSIDE TEMPERATURE
B. TO CALCULATE AIR INFILTRATION HEAT LOSSES:
1. USE THE FOLLOWING VALUES FOR CALCULATION
NUMBER OF AIR EXCHANGES/HR WATT PER °F PER CU. FT.
1/4 .00129
1/2 .00258
3/4 .00387
1 .00516
2 .01032
3 .01548
2. CALCULATE VOLUME OF STRUCTURE = L X W X H (IN CUBIC FEET)
3. MULTIPLY CALCULATED VOLUME X WATT PER DEG F FOR AIR EXCHANGE
4. MULTIPLY RESULT FROM "STEP 3" BY DESIGN TEMPERATURE DIFFERENCE
C. ADD VALUES FOR "A" (HEAT LOSS) AND "B" (INFILTRATION HEAT LOSS)
RESULT = TOTAL HEAT LOSS FOR STRUCTURE
|